Fike Twinflex Pro 8 Zone Fire Alarm Control Panel for Conventional 2-Wire Fire Alarm System

Model No. 5050008 by: Fike.
This item requires:

Free delivery
(over £100 +VAT, applies to zone A and B only, £6 +VAT otherwise)

Normally In Stock

Click & Collect

Order online & collect in store

Our customers love us - read their reviews

Wishlist Ask a question Compare
This is the Fike Twinflex Pro eight zone fire alarm panel (panel only), an intelligent analogue non-addressable panel which is capable of running up to 256 devices. The devices communicate with the control panel using the Twinflex data protocol, which is based on a conventional cabling format. 
A conventional 2-wire fire alarm system is often the natural choice for smaller applications or where budget constraints exist. Fike’s TWINFLEX pro 2-wire fire alarm system has long been known for its adaptability and cost-effectiveness within a variety of applications, big or small, making it one of the most flexible products on the market.
Building on those strengths, and designed for ease of use and state-of-the-art monitoring, the LPCB-Approved TWINFLEXpro is the next generation in 2-wire fire alarm reliability. Two wire installation - only one circuit per zone to connect detectors and sounders - installation savings can be as high as 40%.  This versatile fire alarm panel incorporates Fike’s Multipoint detection system using smoke and heat detectors with built-in sounder, allowing the whole system to be installed using only one pair of wires per zone.
Features and Benefits
  • Alarm control panel Fike Twinflex Pro eight zone (Rafiki)
  • System: 2-wire fire alarm system
  • Highlighted selection menu
  • Front panel LCD display (4 lines x 20 characters)
  • Differentiates between callpoint and detector alarms
  • Event log storing up to 500 events
  • Up to 32 devices per zone
  • Compatibility: this panel is compatible with all previous Rafiki Twinflex devices
  • CE marked, BS EN54-4, BS5839: Part 1: 2002
Technical specs
  • Number Of Zones: 8, Eight Zone Fire Alarm panel
  • Max Zone Length: 500 Meters
  • Zone Loading: 27 SLU (32 Devices Max.)
  • Zone Operating Voltage: 29.9V DC Nominal
  • Standby Battery Requirement: 2 x 3.3Ah 12v Sealed Lead Acid
  • Dimensions: 331 x 331 x 99 mm
  • LCD Display: 4 lines of 20 characters
  • Zone Labels: 12 characters
  • Event log of max. 500 events
  • Max Zone Current: 250mA
  • Operating Temperature: +5C to +40C
  • Mains Supply Range: 230V AC, +10%, -15%, 50/60Hz
  • Inputs: 1 x resistance monitored input (3k3 EOL, 680R firing resistor), 2 x un-monitored inputs
  • Fault Output: 1 x volt free relay (30V DC @ 1A max.)
  • Fire Outputs: 1 x volt free relay (30V DC @ 1A max.), 2 x 24V conventional sounder circuits (10K EOL, 315mA max.)
  • Model: Fike Twinflex Pro 8 Zone Fire Alarm Panel (Rafiki 505 0008)


Follow us for exclusive offers and tips about lighting, switches and sockets

Get in touch

Telephone 020 7263 8007

Fax 020 7272 3007

Sparks Electrical Wholesalers Ltd, 659-661 Holloway Road, Archway, London, N19 5SE, United Kingdom
Registered in England. Company No. 2238028. VAT Reg No: GB 505 6899 17. Copyright © 2003-2016 SparksDirect

Award Winning Ecommerce from Cyber-Duck