Fusebox RTA101030C 10A C-Curve Type A RCBO 30mA 10kA 1 Module
£19.50
Ex. VAT(over £100+VAT, applies to zone A only , £6 +VAT otherwise)
Order online & collect in store
This is the Fusebox RTA101030C 10A C Curve Type A RCBO – 30mA Earth-Leakage & 10kA Overcurrent Protection (Single Module, DIN-Rail) available at SparksDirect.co.uk for the best price.
The Fusebox RTA101030C is a 10A RCBO (Residual Current Breaker with Overcurrent protection) designed to enhance circuit safety by combining an RCD (Residual Current Device) and an MCB (Miniature Circuit Breaker) into a single compact unit. This integrated device protects electrical circuits from dangerous earth-leakage currents that can cause electric shock, as well as from overloads and short circuits that can damage cables, appliances, and infrastructure.
Featuring a C Curve tripping characteristic, the RTA101030C is well-suited for circuits that may see moderate inrush currents — such as motor loads, lighting, or circuits with transient loads — because it trips at roughly 5–10× the rated current before disconnecting. Its Type A residual-current sensitivity detects both AC and pulsating DC leakage faults, offering enhanced protection with modern electronic equipment.
Compact and DIN-rail mountable, this RCBO fits easily into standard 35mm DIN rail consumer units, providing space-saving dual protection that’s compliant with current wiring regulations.
Features and Benefits
- Dual protection (RCD + MCB): Provides combined earth-leakage and overcurrent safety in a single module — reducing components and saving space.
- 10A current rating: Ideal for moderate-load circuits like lighting circuits, dedicated appliance feeds, and socket outlets.
- C Curve tripping characteristic: Balances sensitivity and tolerance for inrush currents, reducing nuisance trips on moderate transient events.
- Type A residual current detection (30mA): Detects AC and pulsating DC leakage currents, enhancing protection for modern electronics.
- 10kA breaking capacity: Handles high fault currents safely, suitable for most domestic and commercial distribution systems.
- Compact single-module design: Maximises usable space on DIN-rail panels.
- Easy installation: DIN-rail mounting with an included insulated neutral lead simplifies wiring.
- Regulation compliant: Meets UK/EU safety standards for consumer electrical systems.
Technical Specifications
- Model: Fusebox RTA101030C — Fusebox C Curve Type A RCBO.
- Device Type: RCBO (Residual Current Breaker with Overcurrent protection).
- Rated Current (In): 10A.
- Tripping Curve: C Curve (5–10× In) — suited for moderate inrush loads.
- Residual Current Type: Type A (detects AC + pulsating DC leakage).
- Residual Trip Sensitivity: 30mA (0.03A).
- Rated Breaking Capacity (Icn): 10kA (10,000A).
- Number of Poles: 1P + N (double-pole switching).
- Rated Voltage: 230V AC, 50/60 Hz.
- Mounting: 35mm DIN-rail mountable.
- Terminal Capacity: 1–16mm² (Live), 1–10mm² (Neutral) typical.
- Flying Neutral Cable: Around 750mm (cut to suit).
- Housing Material: PA6 flame-retardant thermoplastic.
- IP Rating: IP20 — finger-safe interior use.
- Mechanical/Electrical Life: 20,000 / 4,000 operations (typical).
- Standards Compliance: IEC/EN 61009-1 / BS EN 62606.
Three Reasons Customers Recommend This
- All-in-one protection: Combines residual-current and overcurrent safety, eliminating the need for separate RCD and MCB devices.
- Reliable performance: C Curve tripping helps prevent nuisance trips on circuits with moderate transient loads while maintaining safety.
- High fault-handling capacity: 10kA breaking rating means it can interrupt significant fault currents safely — suitable for modern electrical installations.
Who Needs It
- Electricians and electrical contractors specifying individual circuit protection in consumer units, distribution boards, and sub-panels.
- Installers of residential or commercial electrical systems needing compact, dual-function protection that meets current safety codes.
- Maintenance teams or builders upgrading older installations to modern safety standards with combined RCD and MCB devices.
Who Can Install It
- Qualified electricians or competent electrical installers with experience in DIN-rail wiring and UK wiring regulations — internal panel work should be carried out with mains power isolated.
- Not suitable for untrained DIYers: Working inside live electrical panels carries serious risk and requires professional training.
Note: Some images and pictures are for reference only. The item may differ from the image/picture due to manufacturer's change. Should you require the exact item in the picture, please call or email us to enquire.
Shipping
Sparks Direct delivers via courier to the UK only; the standard delivery charge is £6 + VAT for all orders under £100 + VAT. If your order is over £120, you get free delivery (unless there's a special delivery charge for the items you wish to order or you're in shipping zone C or D). Full details for shipping charges can be found via Terms and Conditions.
If the items you order are in stock and the order is placed before 1.00pm, delivery can be made within 1-2 working days. If the items are not in stock, we will inform you via email how long it will take or ask for your confirmation if there's a long lead time.
Returns
We offer 30-day returns for unwanted items - please email us to request a returns number which will need to be quoted when the items are returned. For faulty items or items damaged in transit, please advise via email, and an appropriate returns number will be provided. Full details concerning returns and refunds can be found via our Terms and Conditions.