This is the Apollo 55000-317 conventional smoke detector - a series 65 optical smoke detector, coming without a base (the base needs to be ordered separately).

Note: this item is non-returnable; we are not able to take it back as "unwanted". Please make sure that this is the exact item you require before ordering.

It incorporates a pulsing LED located within the housing of the detector. The external detector moulding is identical to that of the ionisation detector, except that it has an indicator LED which is clear in quiescent state and produces a red light in alarm. They replace the Apollo 60 series, and they can fit within them. 

The Apollo series 65 incorporates well-proven technologies together with advances in materials and electronics technology including an IC based on that used in XP95 analogue addressable detectors (as per the manufacturer's specs). This conventional smoke detector can be integrated into security systems when used with a relay base. 

Note: this optical smoke detector requires a base, like FX340

Apollo 55000-317 Optical Smoke Detector - Features and Benefits 

  • It responds well to slow-burning, smouldering fires
  • This smoke detector is well suited for bedrooms and escape routes
  • Unaffected by wind or atmospheric pressure
  • It comes with a flashing LED and a magnet operated test switch option
  • Well known in the market place, the Apollo 65 series replaces the 60 series, and is considered by many an industry standard.

Apollo Series 65 Smoke Detector - Technical Specs

  • Detector: point type smoke detector (for fire detection and alarm systems for buildings)
  • Sensor: Silicon PIN photo-diode
  • Emitter: GaAs Infra-red ligh emittion diode
  • Sampling frequency: once every 3s
  • Confirmation frequency: once every 2s
  • No of consecutive sensed alarm signals needed to trigger detector alarm: 3
  • Supply voltage: 9V-33V DC
  • Alarm Voltage: 6V to 28V
  • Alarm indicator: clear light emitting diode (LED) emitting red light
  • Holding voltage 6V (min), holding current 10mA (min)
  • Sensitivity: nominal alarm threshold of 0.15dB/m obscuration, measured ina ccordance with EN 54-7: 2000
  • Temperature range: -20deg C to +60 deg C (no condensation or icing)
  • Humidity: 0% to 95% relative humidity. Note: no condensation.
  • Insinsitive to wind or to atmospheric pressure. 
  • IP rating: IP23D, in accordance with BS EN 60529
  • Dimensions: 100mm diameter, 42mm height, in base 100mm diameter x 50mm height.
  • Weight: 99g detector, 150g detector in base. 
  • Materials: the detector housing is of white polycarbonate rated V-0 in accordance with UL, and the terminals are nickel plated stainless steel. 
  • CE Mark

Note: Some images and pictures are for reference only. The item may differ from the image/picture due to manufacturer's change. Should you require the exact item in the picture, please call or email us to enquire.

Need more detailed specs?

Ask a question

Note: HTML is not translated!

How do the Apollo 65 Ionisation and Optical Smoke detectors work?

There are extensive articles covering the Aico Domestic Fire / Smoke / Heat alarms, but not too much on one of the most prolific and popular range, the Apollo Smoke Alarms! We were recently announcing that the Apollo 65 range of Smoke / Heat detectors is back - and here we are with some more useful information concerning how things work in these smoke detectors. There are several types of detecting methods when it comes to the Smoke and the Heat alarms - the Optical, the Ionisation, and the Heat detection. Below you can find a little about each one of the first two of these methods - how do they work and how does the Apollo Series 65 work. How does the Apollo series 65 Ionisation Smoke Detector work? The sensing part of the Series 65 Apollo ionization smoke detector consists of two chambers - an open, outer chamber and a semi-sealed reference chamber within. Mounted in the reference chamber is a low-activity radioactive foil of Americium 241 which enables current to flow between the inner and outer chambers when the detector is powered up. As smoke enters the detector, it causes a reduction of the current flow in the outer chamber and hence an increase in voltage measured at the junction between the two chambers. The voltage increase is monitored by the electronic circuitry which triggers the detector into the alarm state at a preset threshold. An externally visible red LED lights up when the detector changes to an alarm state. An integrating ionization detector, suitable for use in areas where transient levels of smoke may be expected, is also available. How does the Apollo 65 Optical Smoke Detector work? The Apollo series 65 optical smoke detectors incorporate a pulsing LED located in a chamber within the housing of the detector. The chamber is designed to exclude light from any external source. At an angle to the LED is a photodiode which normally does not register the column of light emitted by the LED. In the event of smoke from a fire entering the chamber, the light pulse from the LED will be scattered and hence registered by the photo-diode. If the photo-diode “sees” smoke on the two following pulses, the detector changes into the alarm state and the indicator LED lights up. The detector housing is identical to that of the ionization detector but has an indicator LED which is clear in a quiescent state but produces red light in alarm. [you can get this information from the PDF brochure that Apollo makes available, Apollo Series 65, and if you want to purchase these devices, please visit the Conventional Smoke Alarms section]Buy Apollo Smoke Detectors at Sparks

Shipping

Sparks Direct delivers via courier to the UK only; the standard delivery charge is £6 + VAT for all orders under £100 + VAT. If your order is over £120, you get free delivery (unless there's a special delivery charge for the items you wish to order or you're in shipping zone C or D). Full details for shipping charges can be found via Terms and Conditions.

If the items you order are in stock and the order is placed before 1.00pm, delivery can be made within 1-2 working days. If the items are not in stock, we will inform you via email how long it will take or ask for your confirmation if there's a long lead time.

Returns

We offer 30-day returns for unwanted items - please email us to request a returns number which will need to be quoted when the items are returned. For faulty items or items damaged in transit, please advise via email, and an appropriate returns number will be provided. Full details concerning returns and refunds can be found via our Terms and Conditions.